Capacity
60 KVA
Phase: 3φ4W+PE
System voltage (VDC): 384
Crest factor: >3:1
Input Voltage
380±25%
Output Voltage
380/400/415±1%
Noise Level
<60(within 1 meter)
Alarm
Battery low-voltage, mains abnormal, overload, UPS fault, over-temperature protection
Others
Overload: 125% load keep 10min,150% load keep 30s
Voltage Range
380±25%
Frequency
45~66 Automatically select synchronization range according to grid frequency
Voltage Range
380/400/415±1%, Isolation transformer output
Power Factor
0.9
Type of Wave
Sine Wave, THD<3%
Backup Time
depends on customer configuration
Warranty
1 year
The MaxGreen MGOE-B6033-LF is a high-capacity 60 KVA low-frequency transformer-based online UPS designed for demanding power protection needs in critical environments. Equipped with an IGBT inverter and an output isolation transformer, this UPS ensures high efficiency and reliability by providing clean, stable power. Its online double conversion technology offers continuous power supply by converting AC to DC and back to AC, minimizing power disturbances and ensuring a consistent output. The UPS supports a wide input voltage range of 380V ±25%, making it adaptable to various power conditions. Communication capabilities are enhanced with RS232 and RS485 ports, facilitating easy integration with monitoring and management systems.